                • Pressure restricting angle valve (Spring clip).png
                • Pressure restricting angle valve (Spring clip) 2.png

                Pressure restricting angle valve (Spring clip)


                Price:

                $

                Material:Brass Size:1-1/2" 2-1/2" Pattern:Angle W. pressure: Max inlet 175 psi Surface: Rough / polished / chrome plated Delivery Time:15days~30days

                Categorie:

                Keywords:

                Detailed introduction

                Pressure restricting angle valve (Spring clip)

                Pressure restricting angle valve (Spring clip) is shut off valve, as well as field adjustable flow throttling valve, designed to reduce downstream water pressure under flowing condition. It is equipped with spring clip to control flow and pressure, and the spring clip can be removed for full flow.

                Features and Specification

                Material:Brass
                Size:1-1/2" 2-1/2"
                Pattern:Angle
                W. pressure: Max inlet 175 psi

                Function: FDC outlet, or hose rack assembly

                Surface: Rough / polished / chrome plated

                Available Size

                Notes
                1. 1-1/2″ valve settings range from 1 to 15, used to restrict outlet residual pressure 65 ~ 100 psi at 100 gpm for Class II system.
                2. 2-1/2″ valve settings range from 1 to 20, used to restrict outlet residual pressure 100 ~ 175 psi at 250 gpm for Class I and Class III systems.
                3. The working pressure is 175 psi by UL listed, and 300 psi by FM approved.